WÖHNER 01231 busbar support module

  • For main and outer support in 60 mm busbar systems.
  • Used in industrial power distribution panels and switchgear.
  • Compliant with IEC 61439‑1, UL 508, CSA, and GOST standards.
  • You can become a member here to see prices and take advantage of other privileges.
    The Wöhner 01231 is a 3‑pole busbar support module within the 60Classic system for double‑T section copper bars (approx. 1600 A). It features internal screw holes and no side protection, allowing use as either end or centre support. 
  • IEC Rated current: 1600 A
  • IEC Rated voltage AC: 690 V (UL: 600 V)
  • Max AC voltage: 1000 V
  • Max DC voltage: 1500 V
  • Peak short-circuit current (Ipk): 91 kA
  • Short-time withstand (Icw 1 s): 44 kA
  • UL short-circuit rating: 30 kA unprotected / 200 kA protected
  • Dimensions: 25 × 200 × 123 mm
  • Weight: ≈591 g per pole
  • Material: PA66 + GF (UL94 V‑0, CTI 200), halogen-free; screws galvanized steel, torque: 4 Nm.